Part Number Hot Search : 
4AC13 1M2D3XTR GT5G102 F1001 P6SMB2 P6SMB2 74LV03D LBT14065
Product Description
Full Text Search
 

To Download TMP120-30 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 TRUMPower
D E S C R IP T IO N
The TMP120 series of AC/DC switching power adapters are for 96 to 120 watts of continuous output power. They are enclosed in a 94V-1 rated case with an IEC 320/C14 or C18 inlet to mate with interchangeable AC power cord for world-wide use. All models meet CISPR 11 and FCC class B emission limits, and are designed for medical applications.
120 WATT MEDICAL POWER ADAPTERS
TMP120 SERIES
Class I, Class II
(LVD)
RoHS
F E AT U R E S
Low safety ground leakage current Optional output connectors 100% burn-in 9 0 t o 2 6 4 VAC w i d e i n p u t r a n g e O v e r v o l ta g e a n d o v e r c u r r e n t p r o t e c t i o n s Optional IEC 320/C18 inlet with class II insulation C o m p l i a n t w i t h C E C a n d E n e r g y S ta r e f f i c i e n c y l e v e l I V r e q u i r e m e n ts No load power consumption less than 0.5W Av e r a g e a c t i v e e f f i c i e n c y 8 5 % C o m p l i a n t w i t h R o H S r e q u i r e m e n ts
S a f e t y Sta n d a r d A p p r o va l s
UL 60601-1 CSA C22.2 No. 601.1
TUV EN60601-1
I N P U T S P E C I F I C AT I O N S
I n p u t v o l ta g e Input frequency Input current 90 to 264VAC 47 to 63Hz 1.60A (rms) for 115 VAC 0.80A (rms) for 230 VAC
GENERAL SPECIFICATIONS
Switching frequency Power factor Efficiency Hold-up time Line regulation Inrush current 50KHz ~ 110KHz 0.98 typical at 115VAC 85% min. 15 msec minimum at 115VAC 0.5% maximum at full load
90A max. @ 115 VAC/60Hz Earth leakage current 150A max. @ 230 VAC/50Hz (Class I) E n c l o s u r e l e a k a g e c u r r e n t : 90A max. @ 264 VAC/50Hz (Class II)
OUTPUT SPECIFICATIONS
Output voltage/current Total output power Ripple and noise Overvoltage protection See rating chart 120 watts maximum 2% peak to peak maximum Provided on output #1 only; set at 112 -140% of its nominal output voltage All outputs protected to short circuit conditions All outputs 0.04%/C maximum Maximum excursion of 4% or better on all models, recovering to 1% of final value within 500s after a 25% step load change
Overcurrent protection Temperature coefficient Transient response
60 amps @ 115VAC or 90 amps @230VAC, at 25C cold start Withstand voltage 4000VAC from input to output 1500VAC from input to ground 500VAC from output to ground MTBF 150,000 hours minimum at full load at 25C ambient, calculated per MIL-HDBK-217F EMC Performance (EN60601-1-2: 2001) E N 5 5 0 11 : Class B conducted, Class B radiated FCC: Class B conducted, Class B radiated VCCI: Class B conducted, Class B radiated EN61000-3-2: Harmonic distortion, Class A and D EN61000-3-3: Line flicker EN61000-4-2: ESD, 8KV air and 6KV contact EN61000-4-3: EN61000-4-4: EN61000-4-5: EN61000-4-6: EN61000-4-8: E N 6 1 0 0 0 - 4 - 11 : Radiated immunity, 3V/m Fast transient/burst, 2KV Surge, 1KV diff, 2KV com. Conducted immunity, 3Vrms Magnetic field immunity, 3A/m Voltage dips, 30% reduction for 500ms, 60% reduction for 100ms and >95% reduction for 10ms
E N V I R O N M E N TA L S P E C I F I C AT I O N S
Operating temperature Storage temperature Relative humidity Derating 0 C t o + 6 0 C - 4 0 C t o + 8 5 C 5% to 95% non-condensing Derate from 100% at +40C linearly to 50% at +60C
Tumbler Technologies + TRUMPower
3350 Scott Blvd., Bldg. 13, Santa Clara, California 95054, USA Phone: 408-988-6616 Fax: 408-988-6622 email: sales@trumpower.com Website: www.TRUMPower.com
MEDICAL GRADE
OUTPUT VOLTAGE/CURRENT RATING CHART
Output Product No. TMP120-12 TMP120-15 TMP120-18 TMP120-19 TMP120-20 TMP120-24 TMP120-30 TMP120-36 TMP120-48 NOTES: Vnom. 12V 15V 18V 19V 20V 24V 30V 36V 48V Imin. 0A 0A 0A 0A 0A 0A 0A 0A 0A Imax. 8.0A 7.0A 6.67A 6.32A 6.0A 5.0A 4.0A 3.34A 2.5A
TMP120 SERIES
Tol. 5% 5% 5% 5% 5% 5% 5% 5% 5% Maximum Output Power 96W 105W 120W 120W 120W 120W 120W 120W 120W
1. Ripple and noise: Peak-to-peak with 20MHz bandwidth and 10F tantalum capacitor in parallel with a 0.1F ceramic capacitor at rated line voltage and load ranges. 2. To order a model with IEC320/C18 inlet and class II insulation, add "C2", e.g. TMP120-12-C2.
MECHANICAL SPECIFICATIONS
NOTES: 1. Dimensions shown in inch [mm] 2. Tolerance 0.02 [0.5] maximum 3. Weight: 780 grams approx. 4. Standard output connector is a male 4-pin power DIN. Please consult TRUMPower for other connector options 5. TMP120-12 and TMP120-15 output connectors are without lock.
PIN CHART
PIN Product No. TMP120-12 TMP120-18 TMP120-20 TMP120-30 TMP120-48 TMP120-15 TMP120-19 TMP120-24 TMP120-36
1
2
3
4
Shell
Return
Output +V
Return
Output +V
AC Ground
Tumbler Technologies + TRUMPower
3350 Scott Blvd., Bldg. 13, Santa Clara, California 95054, USA Phone: 408-988-6616 Fax: 408-988-6622 email: sales@trumpower.com Website: www.TRUMPower.com


▲Up To Search▲   

 
Price & Availability of TMP120-30

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X